AMF Panel Manufacturer (Auto Mains Failure)
An AMF (auto mains failure) panel starts the diesel generator when the mains supply fails and moves the load on to it, with no operator. When the mains returns it moves the load back and stops the DG. APJ Engineers builds AMF panels and supplies DG sets with full installation at its works in Vasai, near Mumbai.

The AMF sequence
- The panel senses loss of mains (or low / unbalanced voltage)
- After a set delay it cranks the DG and waits for healthy voltage and frequency
- It opens the mains breaker and closes the DG breaker, so the load is on the DG
- When mains is healthy again for a set time, it transfers the load back
- It runs the DG off-load to cool, then stops it and waits for the next failure
The mains and DG breakers are interlocked electrically and mechanically so the two sources can never be connected together.
What goes into it
Two interlocked breakers or contactors (mains and DG), an AMF controller or PLC, voltage sensing, battery charger, metering, and DG protection and alarms. Auto, manual and test modes are standard.
What APJ builds
AMF panels with PLC-based auto mains failure logic for DG sets from 15 kVA to 3000 kVA, as stand-alone panels or as part of a main LT panel. APJ also supplies the DG set, acoustic enclosure and synchronising panel, and installs, tests and commissions the system on site.
See DG sets and SITC and DG synchronising panels.
What to send for a quotation
- Single-line diagram (SLD) or BOQ
- Incomer rating and the fault level at the board
- Preferred switchgear make, busbar material (copper or aluminium) and IP rating
- Cable entry (top or bottom) and any size limit at site
- Delivery location and the date you need it
The full list is in our quotation checklist.
Tested before it leaves
Every panel gets an IEC 61439-1 factory acceptance test with recorded readings, photos and a video, witnessed by the client where they wish. Its FAT QR then opens the full record, including later site and service reports.
How our traceability worksType-test certificates
- ASTA 6300 A / 85 kA (forced-cooled)
- ASTA 4000 A / 65 kA
- CPRI 4000 A / 65 kA
- ERDA temperature-rise test, 4000 A
- ERDA IP65 and IP55
- ASTA internal arc, 85 kA for 0.5 s
Request a quotation
Tell us what you need. Your request goes straight to our sales team.
Frequently asked questions
What is the difference between an AMF panel and an ATS?
An ATS (automatic transfer switch) only transfers the load between two sources. An AMF panel also starts and stops the DG set and monitors it. Many AMF panels use an ATS or two interlocked breakers for the transfer.
How long does the changeover take?
It depends on the DG's starting time and the delays set in the controller. The delays are adjustable and are set during commissioning to suit the site.
Can one AMF panel handle more than one DG?
For two or more DG sets running together you need a synchronising panel, which also does the mains-failure start.
Where are APJ panels made?
At APJ Engineers' own works at Pelhar, Vasai (Palghar district), near Mumbai: Plot No. 333, Pelhar Village, Opp. Apple Industries, Nalasopara Highway Road, Vasai (East), Palghar, Maharashtra 401208, India.
Is every panel tested before dispatch?
Yes. Every panel gets a factory acceptance test (FAT): IEC 61439-1 routine verification with recorded readings, photos and a test video, using instruments with current calibration certificates. A panel is released for dispatch only after its FAT is passed.
Can I check the test record of my panel?
Yes. Each panel carries a FAT QR code. Scan it, or type the code under it on apje.in, to open that panel's FAT report, drawings and site reports.
Do you supply outside Mumbai?
Yes. APJ supplies across India, with on-site supply, installation, testing and commissioning (SITC) teams.
How do I get a quotation?
Send your single-line diagram or BOQ on WhatsApp (+91-9967717710), call +91-9819917710, or email apj@apje.in.