Forms of internal separation in LT panels: Form 1 to Form 4b
A short guide for consultants, contractors and buyers of LT switchboards. By APJ Engineers, Vasai.
The form of internal separation says how far the inside of a switchboard is divided by barriers or partitions. IEC 61439-2 defines the forms. A higher form does not make a panel carry more current or withstand a bigger fault. It decides how safely someone can work on one part of the board while the rest stays live, and how far a fault in one compartment can spread.
Three things that can be separated
- Busbars: the main and distribution bars
- Functional units: each feeder with its breaker or starter
- Terminals: where the outgoing cables are connected
The forms differ in which of these are separated from which.
The forms, one by one
- Form 1: no internal separation.
- Form 2a: busbars are separated from the functional units. Terminals are not separated from the busbars.
- Form 2b: busbars are separated from the functional units, and the terminals are separated from the busbars.
- Form 3a: busbars are separated from the functional units, and the functional units from one another. Terminals are separated from the functional units, but not from the busbars or from each other.
- Form 3b: as Form 3a, with the terminals also separated from the busbars. The terminals of different feeders still share a space.
- Form 4a: as Form 3b, and each feeder's terminals are separated from those of other feeders. The terminals are in the same compartment as their own functional unit.
- Form 4b: as Form 4a, but each feeder's terminals are in their own enclosed space, outside the compartment of the functional unit.
What separation protects against
The standard gives two aims: protection against contact with hazardous live parts of the neighbouring units, and protection against solid objects passing from one unit to the next. In practice this means a dropped tool or a loose cable lug in one feeder cannot reach the busbars or another feeder.
How to choose
- Small distribution boards that are switched off for any work: Form 1 or Form 2 is common.
- MCCs: Form 3b is widely used, so one starter can be worked on with the others in service.
- Main PCCs and critical boards (hospitals, data centres, process plants): Form 3b or Form 4b, so that cables of one feeder can be terminated while the rest of the board is live.
A higher form needs more sheet metal, more space and more assembly time, so the board is larger and costs more. The standard leaves the form to agreement between the buyer and the manufacturer. Write it in the specification and on the single-line diagram.