APJ EngineersAPJ WhatsApp

LT panel quotation checklist: what to send the manufacturer

Send these with your enquiry and quotations from different makers will be like for like. By APJ Engineers, Vasai.

Two quotations for the same panel can differ widely because each maker filled the gaps in the enquiry differently. The list below closes those gaps. If you do not have an item, say so, and the maker can propose it and state the assumption.

1. The single-line diagram or BOQ

The SLD is the most useful document. It should show every incomer and outgoing feeder with its rating, the breaker type (ACB, MCCB, MCB), poles, metering and any interlocks. A BOQ with the same information also works.

2. Electrical data

3. Construction

4. Components

5. Standards, tests and inspection

State the standard (IEC 61439-1 and -2) and which type-test evidence you need to see. Say whether you or a third party will witness the factory acceptance test. Our guide to design and routine verification explains what to ask for.

6. Commercial

Send it to APJ

WhatsApp the SLD or BOQ to +91-9967717710 or email apj@apje.in. See LT panels for what we build.

Frequently asked questions

What is the minimum needed for a budgetary LT panel quotation?

A single-line diagram or feeder list with ratings, the fault level, the preferred switchgear make and the delivery location.

Why do quotations for the same panel differ so much?

Usually because the enquiry left out the fault level, form of separation, busbar material or switchgear make, and each maker assumed something different.

How do I find the fault level at my panel?

Your electrical consultant calculates it from the transformer rating and impedance and the cable between transformer and panel. If you send the transformer details, the panel maker can estimate it.